Battery Charging

Constant Current (CC) Charging Constant current charging
ensures 100% state of charge. Normally used for battery testing,
commissioning or maintenance. Rarely used in service. By
charging more than 140% of rated Ah capacity, cell can be fully
charged.

Normal Charging : 0.2C Amps for 8 Hrs
Maximum Charging rate:
KPL 0.3C5A
KPM 0.3C5A
KPH 0.5C5A

High rate charging to be avoided at the end of charging. There is risk of electrolyte over flow due to heavy gassing.

Float cum Boost Charging

Cells are normally on float at following voltages
KPL,KPM, KPH - 1.40 to 1.42 Volt/cell

Minimum 2mA per Ah current required to compensate for self
discharge. Negligible water loss on float but require boost
charging at 6 monthly intervals & after discharge. Cells to be boost charged at following voltage:

KPL - 1.50 to 1.65 Volt/cell
KPM, KPH - 1.47 to 1.62 Volt/cell

It is preferred to boost at higher voltages (1.60 to 1.65 vpc). More that 95% capacity can be restored within 8 hrs after
emergency discharge.

A significant fall of current is indication that battery is more
than 95% charged & can be switched to float. Boost charging
setting more than 1.65 vpc can overcharge battery leading to
excess water losses due to voltage window restrictions or
charger’s limitation batteries can be boosted at low voltages (1.45 to 1.50 vpc) Batteries can be recharged to 85 to 90 % capacity at low voltages.

Single stage charging

For fully automatic operation cells are floated at higher voltages. Periodic boosting or boost charging after emergency
discharge is not required. Recommended voltages for single
stage float charging are:

KPL - 1.48 to 1.60 Volt/cell
KPM - 1.47 to 1.57 Volt/cell
KPH - 1.45 to 1.53 Volt/cell

All type of cells for starting application - 1.50 to 1.55 Volt/cell
More than 80% capacity can be restored within 5 hrs after
emergency discharge. Depending upon float voltage cells can
achieve 90to 98% state of charge in 24 hrs. Water losses are higher than in case of float cum boost charging.

Commissioning charge /
Service boost charging

Battery is required to attain 100% state of charge for commissioning, testing & maintenance (cell changing). This can be ensured by constant current charging only. To maintain constant current minimum voltage should be 1.72, 1.70 & 1.68 VPC respectively for KPL, KPM & KPH. If charger voltage is inadequate, battery is split into two banks and charged.

Cost Benefit Analysis

  • Saving in maintenance cost and operating cost.
  • Saving in replacement cost (one  battery against 3 to 4 numbers of lead acid batteries).
  • Saving in space for battery room and reduced cost requiring no special flooring, ventilation, air
    conditioning.
  • Possibility to house battery in cabinet along with Electronics.
  • No need for refreshing charge.
  • No possibility of sulphation and no sudden failure and hence no loss in production.

Growing Demand

  • Because of the cost advantage in the long run, nickel cadmium battery demand is increasing
    year by year.
  • With India, expanding in various infrastructure, power, oil exploration etc., There is a growing demand for GBPL nickle cadmium batteries.
  • Department like Railway Export Metro, diesel locomotive are switching over from lead acid to
    nickel cadmium batteries.